| Performance Data: Model OWC-5 |
Specifications |
Nominal Capacity (Tons) -
Standard Conditions of 95° |
5 |
| Delivered Cooling Capacity, BTU/H |
60,000 |
| Waste Oil, BTH/H Input |
150,000 |
| Gal. per hr. Consumption |
1 |
| Chilled Water Data |
| Return Water Temperature |
55.0°F |
| Supply Water Temperature |
45.0°F |
| Chilled Water Flow, GPM |
12.0 |
Allowable External Friction -
Loss for Piping & Coil, Feet of Water |
25 |
| Chiller Electrical |
| Required Voltage, 60Hz, Single Phase |
208/230 |
| Condenser Fan Motor |
1/2 hp |
| Full Load/Locked Rotor Amps |
3.5/7.2 |
| 1 Free Air Fan 1@1/4 hp |
1.0 |
| Chiller Only KW Consumption |
2.15 |
| Minimum Circuit Ampacity (MCA) |
9.81 |
| Maximum Over Current Protection (MOCP) |
20 amp |
| Electrical Entrance Knockouts, Diameter |
7/8" |
| Waste Oil Burner Electrical |
| Voltage 60Hz (one leg) |
230V |
| Burner Motor 1/4 hp |
2.2 |
| Transformer amps |
.35 |
| Oil Supply Pump Motor amps |
.62 |
| Heater Element amps |
2.0 |
| Oil Primary Control amps |
.2 |
| Burner amps avg. |
6.7 |
| Burner only KW |
1.25 |
| Combine total unit amps; Chiller with Burner |
avg. 15.5 |
| Combine total unit kw; Chiller with Burner |
3.41 |
| Dimensions (L x W x H) |
91" x 51" x 33.5" |
| Weight |
930 lbs. |
| Shipping Weight |
980 lbs. |